Solved Examples of Proper Wire & Cable Size: Solution
Solved Examples of Proper Wire & Cable Size: Solution
Following are the examples of determining the proper Size of cables for electrical wiring
installation which will make it easy to understand the method of “how to determine the
proper size of cable for a given load”.
Example 1 … (Imperial, British or English System)
For Electrical wiring installation in a building, Total load is 4.5kW and total length of
cable from energy meter to sub circuit distribution board is 35 feet. Supply voltages are
220V and temperature is 40°C (104°F). Find the most suitable size of cable from energy
meter to sub circuit if wiring is installed in conduits.
Solution:-
Total Load = 4.5kW = 4.5 x1000W = 4500W
20% additional load = 4500 x (20/100) = 900W
Total Load = 4500W + 900W = 5400W
Total Current = I = P/V = 5400W /220V =24.5A
Now select the size of cable for load current of 24.5A (from Table 1) which is 7/0.036
(28 Amperes). It means we can use 7/0.036 cable according to table 1.
Now check the selected (7/0.036) cable with temperature factor in Table 3, so the
temperature factor is 0.94 (in table 3) at 40°C (104°F) and current carrying capacity of
(7/0.036) is 28A, therefore, current carrying capacity of this cable at 40°C (104°F) would
be;
Current rating for 40°C (104°F) = 28 x 0.94 = 26.32 Amp.
Since the calculated value (26.32 Amp) at 40°C (104°F) is less than that of current
carrying capacity of (7/0.036) cable which is 28A, therefore this size of cable (7/0.036)
is also suitable with respect to temperature.
Now find the voltage drop for 100 feet for this (7/0.036) cable from Table 4 which is 7V,
But in our case, the length of cable is 35 feet. Therefore, the voltage drop for 35 feet
cable would be;
Actual Voltage drop for 35 feet = (7 x 35/100) x (24.5/28) = 2.1V
And Allowable voltage drop = (2.5 x 220)/100 = 5.5V
Here The Actual Voltage Drop (2.1V) is less than that of maximum allowable voltage
drop of 5.5V. Therefore, the appropriate and most suitable cable size is (7/0.036) for
that given load for Electrical Wiring Installation.
Related Post: How to Wire Auto & Manual Changeover & Transfer Switch? (1 & 3
Phase)
Example 2 … (SI / Metric / Decimal System)
What type and size of cable suits for given situation
Load = 5.8kW
Volts = 230V AV
Length of Circuit = 35 meter
Temperature = 35°C (95°F)
Solution:-
Load = 5.8kW = 5800W
Voltage = 230V
Current = I = P/V = 5800 / 230 = 25.2A
20% additional load current = (20/100) x 5.2A = 5A
Total Load Current = 25.2A + 5A = 30.2A
Now select the size of cable for load current of 30.2A (from Table 1) which is 7/1.04 (31
Amperes). It means we can use 7/0.036 cable according to the table 1.
Now check the selected (7/1.04) cable with temperature factor in Table 3, so the
temperature factor is 0.97 (in table 3) at 35°C (95°F) and current carrying capacity of
(7/1.04) is 31A, therefore, current carrying capacity of this cable at 40°C (104°F) would
be;
Current rating for 35°C (95°F) = 31 x 0.97 = 30 Amp.
Since the calculated value (30 Amp) at 35°C (95°F) is less than that of current carrying
capacity of (7/1.04) cable which is 31A, therefore this size of cable (7/1.04) is also
suitable with respect to temperature.
Now find the voltage drop for per ampere meter for this (7/1.04) cable from (Table 5)
which is 7mV, But in our case, the length of cable is 35 meter. Therefore, the voltage
drop for 35 meter cable would be:
Actual Voltage drop for 35meter =
= mV x I x L
= (7/1000) x 30×35 = 7.6V
And Allowable voltage drop = (2.5 x 230)/100 = 5.75V
Here the actual Voltage drop (7.35V) is greater than that of maximum allowable voltage
drop of 5.75V. Therefore, this is not a suitable size of cable for that given load. So we
will select the next size of selected cable (7/1.04) which is 7/1.35 and find the voltage
drop again.
According to Table (5) the current rating of 7/1.35 is 40 Amperes and the voltage drop in
per ampere meter is 4.1 mV (See table (5)). Therefore, the actual voltage drop for 35
meter cable would be;
Actual Voltage drop for 35 meter =
= mV x I x L
(4.1/1000) x 40×35 = 7.35V = 5.74V
This drop is less than that of maximum allowable voltage drop. So this is the most
appropriate and suitable cable or wire size.
Related Posts:
How to Connect a Portable Generator to the Home Supply – 4 Methods
How to Connect Automatic UPS / Inverter to the Home Supply System?
Example 3
Following Loads are connected in a building:-
Sub-Circuit 1
2 lamps each o 1000W and
4 fans each of 80W
2 TV each of 120W
Sub-Circuit 2
6 Lamps each of 80W and
5 sockets each of 100W
4 lamps each of 800W
If supply voltages are 230 V AC, then calculate circuit current and Cable size for
each Sub-Circuit?
Solution:-
Total load of Sub-Circuit 1
= (2 x 1000) + (4 x 80) + (2×120)
= 2000W + 320W + 240W = 2560W
Current for Sub-Circuit 1 = I = P/V = 2560/230 = 11.1A
Total load of Sub-Circuit 2
= (6 x 80) + (5 x 100) + (4 x 800)
= 480W + 500W + 3200W= 4180W
Current for Sub-Circuit 2 = I = P/V = 4180/230 = 18.1A
Therefore, Cable suggested for sub circuit 1 = 3/.029” (13 Amp) or 1/1.38 mm (13
Amp)
Cable suggested for Sub-Circuit 2 = 7/.029” (21 Amp) or 7/0.85 mm (24 Amp)
Total Current drawn by both Sub-Circuits = 11.1A + 18.1A = 29.27 A
So cable suggested for Main-Circuit = 7/.044″ (34 Amp) or 7/1.04 mm (31 Amp)
Related Posts:
American Wire Gauge “AWG” Chart – Wire Size & Ampacity Table
American Wire Gauge (AWG) Calculator – AWG Size Chart & Table
Standard Wire Gauge “SWG” Calculator – SWG Size Chart & Table
Example 4
A 10H.P (7.46kW) three phase squirrel cage induction motor of continuous rating using
Star-Delta starting is connected through 400V supply by three single core PVC cables
run in conduit from 250feet (76.2m) away from multi-way distribution fuse board. Its full
load current is 19A. Average summer temperature in Electrical installation wiring is 35°C
(95°F). Calculate the size of the cable for the motor?
Solution:-
Motor load = 10H.P = 10 x 746 = 7460W *(1H.P = 746W)
Supply Voltage = 400V (3-Phase)
Length of cable = 250feet (76.2m)
Motor full load Current = 19A
Temperature factor for 35°C (95°F) = 0.97 (From Table 3)
Now select the size of cable for full load motor current of 19A (from Table 4) which is
7/0.36” (23 Amperes) *(Remember that this is a 3-phase system i.e. 3-core cable) and
the voltage drop is 5.3V for 100 Feet. It means we can use 7/0.036 cable according
Table (4).
Now check the selected (7/0.036) cable with temperature factor in table (3), so the
temperature factor is 0.97 (in table 3) at 35°C (95°F) and current carrying capacity of
(7/0.036”) is 23 Amperes, therefore, current carrying capacity of this cable at 40°C
(104°F) would be:
Current rating for 40°C (104°F) = 23 x 0.97 = 22.31 Amp.
Since the calculated value (22.31 Amp) at 35°C (95°F) is less than that of current
carrying capacity of (7/0.036) cable which is 23A, therefore this size of cable (7/0.036) is
also suitable with respect to temperature.
Load factor = 19/23 = 0.826
Now find the voltage drop for 100feet for this (7/0.036) cable from table (4) which is
5.3V, But in our case, the length of cable is 250 feet. Therefore, the voltage drop for 250
feet cable would be;
Actual Voltage drop for 250feet = (5.3 x 250/100) x 0.826 = 10.94V
And maximum Allowable voltage drop = (2.5/100) x 400V= 10V
Here the actual Voltage drop (10.94V) is greater than that of maximum allowable
voltage drop of 10V. Therefore, this is a not a suitable size of cable for the given load.
So we will select the next size of selected cable (7/0.036) which is 7/0.044 and find the
voltage drop again. According to Table (4) the current rating of 7/0.044 is 28 Amperes
and the volt drop in per 100 feet is 4.1V (see Table 4). Therefore, the actual voltage
drop for 250 feet cable would be;
Actual Voltage drop for 250 feet =
= Volt drop per 100 feet x length of cable x load factor
= (4.1/100) x 250 x 0.826 = 8.46V
And Maximum Allowable voltage drop = (2.5/100) x 400V= 10V
The actual voltage drop is less than that of maximum allowable voltage drop. So this is
the most appropriate and suitable cable size for electrical wiring installation in a given
situation.
NEC Wire Size Table 310.15(B)(16) (formerly Table
310.16) & Chart
NEC (National Electrical Code) Table 310.15(B)(16) (formerly Table 310.16) – 310.60 –
ARTICLE 310 – Conductors for General Wiring & Allowable Ampacities of Conductors &
Wire Sizes based on AWG (American Wire Gauge).
310.60 ARTICLE 310 — CONDUCTORS FOR GENERAL WIRING
Table 310.15(B)(16) (formerly Table 310.16) Allowable Ampacities of Insulated
Conductors Rated Up to and Including 2000 Volts, 60°C Through 90°C (140°F
Through 194°F), Not More Than Three Current-Carrying Conductors in Raceway,
Cable, or Earth (Directly Buried), Based on Ambient Temperature of 30°C (86°F)*